For Contractors & Builders

Installation Guides &
Rough-In Requirements

Rough-in requirements, clearance specs, electrical and gas requirements, and installation notes for every Bromic product family. Use this page to plan your rough-in before the heaters arrive on site.

This page provides general installation guidance. Always refer to the official Bromic instruction manual for your specific product and model. Gas line work must be performed by a licensed gas contractor. Electrical work must comply with local codes.

Tungsten Smart-Heat® Electric

2000W3000W4000W6000W
Official Manual

RRough-In Requirements

Electrical

220-240V dedicated circuit (208V available). 2000W: 10A; 3000W: 15A; 4000W: 20A; 6000W: 30A. Hardwired. No plug connection.

Conduit / Wiring

Conduit entry from rear or side. Confirm entry point before rough-in. Provide junction box within 12" of mounting point.

Mounting

Ceiling mount: 8" minimum clearance above unit to structure. Wall mount: bracket supplied. Recess kit available for flush ceiling install.

Minimum Clearances

Min. floor clearance (wall mount)72" (6 ft)
Min. floor clearance (ceiling mount)96" (8 ft)
Side clearance to combustibles24"
Front clearance to combustibles36"
Rear clearance to structure8" (ceiling) / 4" (wall)

NInstallation Notes

IPX4 rated. Suitable for covered outdoor areas. Not rated for direct rain exposure.

4000W and 6000W models have dual heating elements that can be controlled independently.

Recess kit requires minimum 5" ceiling depth. Confirm before specifying flush mount.

Dimmer controller requires compatible wiring. Confirm before rough-in if dimming is specified.

Full Specifications

View Spec Sheet

Tungsten Smart-Heat® Gas

300 Series (26,000 BTU)500 Series (43,000 BTU)
Official Manual

RRough-In Requirements

Gas Supply

Natural gas or LPG. Minimum supply pressure: 7" WC (natural gas) / 11" WC (LPG). Maximum inlet pressure: 14" WC. 1/2" NPT gas connection.

Electrical

110V / 2A for ignition and controls. Standard outlet or hardwired junction box within 6 ft of unit.

Mounting

Wall or ceiling mount via pivot bracket. Ceiling post mount available. Gas supply line must reach mounting point. Confirm before rough-in.

Minimum Clearances

Min. floor clearance96" (8 ft)
Side clearance to combustibles24"
Front clearance to combustibles36"
Rear clearance to structure12"
Below combustibles24"

NInstallation Notes

Wind resistant to 8 mph. For more exposed installations, consider Platinum Gas (12 mph rated).

Direct ignition. No pilot light. Requires 110V electrical connection for ignition.

Pivot bracket allows 25° tilt in each direction. Confirm desired aim angle before mounting.

Gas line must be installed by a licensed gas contractor. PHD can coordinate.

Heat deflector accessory available for installations where downward heat deflection is needed.

Full Specifications

View Spec Sheet

Platinum Smart-Heat® Electric

2300W3400W4500W
Official Manual

RRough-In Requirements

Electrical

220-240V dedicated circuit (208V available). 2300W: 12A; 3400W: 16A; 4500W: 22A. Hardwired. No plug connection.

Conduit / Wiring

Conduit entry from rear. Provide junction box within 12" of mounting point. Confirm entry orientation before ceiling rough-in.

Mounting

Ceiling or wall mount. Standard recess kit requires 5" ceiling depth. Low-clearance recess kit available for shallower ceilings (confirm depth). Pole mount available.

Minimum Clearances

Min. floor clearance (wall mount)72" (6 ft)
Min. floor clearance (ceiling mount)96" (8 ft)
Side clearance to combustibles18"
Front clearance to combustibles36"
Rear clearance to structure6" (surface mount) / flush (recess)

NInstallation Notes

IPX4 rated. 304 stainless steel construction. Schott ceramic-glass fascia.

Low-clearance recess kit available for ceilings under 5" depth. Specify at order.

Adjustable mounting brackets allow tilt angle adjustment after installation.

Compatible with Affinity Dimmer Controller. Confirm wiring before rough-in.

Available in black or white. Specify finish at order. Finish cannot be changed after installation.

Full Specifications

View Spec Sheet

Platinum Smart-Heat® Gas

300 Series (23,600 BTU)500 Series (39,800 BTU)
Official Manual

RRough-In Requirements

Gas Supply

Natural gas or LPG. Minimum supply pressure: 7" WC (natural gas) / 11" WC (LPG). 1/2" NPT gas connection. Gas line must reach mounting point.

Electrical

110V / 2A for ignition. Standard outlet or hardwired junction box within 6 ft of unit.

Mounting

Wall or ceiling mount via pivot bracket. Ceiling post mount available. Confirm gas supply routing before mounting point is finalized.

Minimum Clearances

Min. floor clearance96" (8 ft)
Side clearance to combustibles24"
Front clearance to combustibles36"
Rear clearance to structure12"
Below combustibles24"

NInstallation Notes

Wind resistant to 12 mph. Best choice for more exposed outdoor installations.

Ceramic-glass screen creates a warm ambient glow. Confirm client expectation before specifying.

Heat deflector accessory available for installations requiring downward heat deflection.

Available in black or stainless finish. Specify at order.

Gas line must be installed by a licensed gas contractor.

Full Specifications

View Spec Sheet

Eclipse Smart-Heat® Electric

2900W (208V)2900W (240V)
Official Manual

RRough-In Requirements

Electrical

208V or 240V dedicated circuit. 2900W: 15A (240V) / 16A (208V). Hardwired. Conduit entry from top of pole or ceiling canopy.

Mounting

Six mounting configurations: 24" twin pole (standard), wall mount pole, 8" / 24" / 48" straight poles, curved pole. Confirm pole selection before rough-in. Conduit routing differs by configuration.

Lighting Circuit

LED circuit is integrated. No separate lighting circuit required. Affinity Eclipse Controller required for dimming functionality.

Minimum Clearances

Min. floor clearance (wall mount)96" (8 ft)
Min. floor clearance (ceiling mount)96" (8 ft)
Side clearance to combustibles24"
Front clearance to combustibles36"

NInstallation Notes

Pendant design. Confirm ceiling height and desired hanging height before specifying pole length.

Affinity Eclipse Controller required for LED dimming. Standard On/Off controller does not dim LEDs.

Available in matte black only.

Freestanding version available. No rough-in required. Requires 220-240V outlet within reach.

LED color: warm white 3000K, 497 lm dimmable.

Full Specifications

View Spec Sheet

Cobalt Smart-Heat™ Electric

4000W (208V / 220-240V)6000W (208V / 220-240V)
Official Manual

RRough-In Requirements

Electrical

208V or 220-240V dedicated circuit. 4000W: 20A; 6000W: 30A. Hardwired. No plug connection.

Conduit / Wiring

Conduit entry from rear. Provide junction box within 12" of mounting point.

Mounting

Wall or ceiling mount. Adjustable bracket included. No recess kit available for this model.

Minimum Clearances

Min. floor clearance (wall mount)72" (6 ft)
Min. floor clearance (ceiling mount)96" (8 ft)
Side clearance to combustibles24"
Front clearance to combustibles36"

NInstallation Notes

IPX4 rated. 304 stainless steel. Silver/stainless finish only.

Entry-level price point. Good choice for projects where budget is a primary constraint.

Compatible with Affinity On/Off and Dimmer controllers.

No recess kit available. Surface mount only.

Full Specifications

View Spec Sheet

Controls & Wiring

Affinity Smart-Heat® Controls

Compatibility, wiring requirements, and notes for every Bromic control option. Confirm control selection before electrical rough-in.

Affinity On/Off Controller

BH0200001

Compatible With

Tungsten ElectricPlatinum ElectricCobalt ElectricTungsten GasPlatinum Gas

Wiring

Single-pole switch wiring. 240V max. Requires neutral wire at switch location.

Notes

Controls up to 6 heaters per zone. Expansion board required for more than 6 units.

Affinity Dimmer Controller

BH0200002

Compatible With

Tungsten ElectricPlatinum ElectricCobalt Electric

Wiring

240V dimmer wiring. Requires neutral wire. Not compatible with gas heaters.

Notes

Dims heat output proportionally. Confirm heater model supports dimming before specifying.

Affinity Eclipse Controller

BH0200003

Compatible With

Eclipse Smart-Heat Electric (ceiling/wall)Eclipse Smart-Heat Freestanding

Wiring

Dedicated Eclipse wiring harness. Controls both heat and LED dimming independently.

Notes

Required for LED dimming on Eclipse models. Standard On/Off controller does not dim LEDs.

Manual Wall Switch

BH0200004

Compatible With

All Bromic heaters

Wiring

Standard single-pole switch wiring. No neutral required.

Notes

On/Off only. No dimming. Simplest control option for single-zone installs.

Affinity Expansion Board

BH0200005

Compatible With

Affinity On/OffAffinity Dimmer

Wiring

Wired in series with Affinity controller. Extends zone capacity by 6 additional heaters.

Notes

Required when a single zone exceeds 6 heaters. Multiple boards can be daisy-chained.

Before You Rough In

Pre-Installation Checklist

Confirm product model and wattage/BTU with PHD before rough-in

Verify ceiling height meets minimum floor clearance requirements

Confirm mounting point location and structure availability

Determine control type (On/Off vs. Dimmer vs. Eclipse) before wiring

For gas: confirm fuel type (NG vs. LPG) and supply pressure

For recess kits: measure ceiling depth before specifying flush mount

For Eclipse: confirm pole length based on desired hanging height

Confirm color/finish at order. Cannot be changed after installation

For multi-zone installs: confirm expansion board requirement

Coordinate delivery timing with PHD before rough-in is complete

Questions Before You Rough In?

Talk to Our Technical Team

We've coordinated hundreds of Bromic installations across the Southeast. If you have a question about rough-in requirements, clearances, or product selection, call us or submit a project inquiry.